NFPA 99 sorts systems by risk category. A dental office with piped nitrous, oxygen, or only dental air and vacuum is Category 3, according to King County's examples. Oral surgery with full sedation is Category 2 (King County). In 2026, installers must hold ASSE 6010 certification, and a separate third party must test the system before use.

Which guide you need: this checklist is for contractors. Owners who want the basics, such as categories, nitrous and what to ask, should read NFPA 99 basics for dental owners.

Key facts

ItemRequirementSource
Typical general dental (piped N2O/O2, or air and vacuum only)Category 3King County
Oral surgery suite with full sedation, piped gasesCategory 2King County
Installer qualificationASSE 6010 certificationUpCodes
Medical gas pipeHard-drawn seamless copper, ASTM B819, Type L or KLas Vegas Fire
LabelsAt least every 20 ft, once per room, both sides of wallsLas Vegas Fire
TestingBy someone other than the installer, before useLas Vegas Fire
Standing pressure test24 hours at 20% above operating; ≤ 0.5% leakageLas Vegas Fire

What category is my dental office?

NFPA 99 2018, section 4.1, defines four risk categories by how badly a failure could hurt someone. Category 1 is major injury or death; Category 4 has no impact on patient care (King County). King County's examples for dental:

  • Dental office with oral surgery suites and full sedation, with piped patient medical gases: Category 2
  • Dental office with piped nitrous oxide and/or oxygen: Category 3
  • Dental office with no general anesthesia and piped dental air and vacuum only: Category 3

(King County)

King County also says a risk assessment should be done (King County). The category decides the rules for sources, alarms and valves, so settle it with the designer and authority having jurisdiction (AHJ) before plan review. The owner-level overview is in NFPA 99 for dental offices.

Who is allowed to install it?

Codes based on NFPA 99 require anyone installing medical gas and vacuum piping to be certified to ASSE 6010. Brazing must be done by qualified individuals (UpCodes). ASSE 6010 candidates need at least four years of documented plumbing or mechanical experience. They complete a training course taught by an ASSE 6050-certified instructor, then pass a 100-question exam and a brazing practical (ASSE 6010 bulletin).

Inspection and verification are separate credentials: ASSE 6020 for inspectors and ASSE 6030 for verifiers (ASPE Denver). Las Vegas asks for the brazer's certificate or qualifications at permit application (Las Vegas Fire).

What materials and installation rules apply?

From the City of Las Vegas checklist (effective January 5, 2026), which cites NFPA 99 sections:

  • Medical gas piping: hard-drawn seamless copper, ASTM B819 medical gas tube, Type L or K.
  • Category 3 vacuum piping: copper Type L, K or M, or stainless steel. Liquids route to sanitary drainage per code.
  • Dental air compressors are located separately from other medical gas systems or storage enclosures, and their intake air is drawn from a location free of contaminants such as vacuum discharge.
  • Pipe and valve labels at intervals of no more than 20 ft, at least once per room, and on both sides of walls.
  • Gas rooms are rated at least one hour, with two exterior-wall vents of at least 36 sq in, one within 6 in of the floor and one within 6 in of the ceiling.

(Las Vegas Fire)

Vacuum piping for chairs is separate from patient gas piping. Air Techniques states its Mojave pumps comply with NFPA 99C level 3 requirements (Air Techniques). Nitrous scavenging needs its own vacuum branch (A-dec). See running dental vacuum lines.

What tests happen before the system is used?

The Las Vegas checklist walks through the NFPA 99 sequence:

  1. Initial pressure test at 1.5 times operating pressure, at least 150 psig, with oil-free dry nitrogen NF. Each joint is checked.
  2. Initial cross-connection test. Every system is reduced to atmospheric pressure and each outlet checked so gas comes only from the system being tested.
  3. Initial purge test. Each outlet is purged until a clean white cloth shows no discoloration.
  4. Standing pressure test for 24 hours at 20% above operating pressure. Leakage can't exceed 0.5% of starting pressure.
  5. Standing vacuum test for 24 hours at 20 inHg.
  6. Alarm tests at 20% above or below normal operating pressure.
  7. Third-party final testing report and system certification.

The testing must be done by someone other than the installing contractor, certified by an independent medical gas testing agency, before the system is used (Las Vegas Fire).

Book the verifier early. Their report gates the final inspection, and the final gates the certificate of occupancy. Log it in the permit & inspection tracker (free tool, coming soon). Mark gas outlets, zone valves and alarm panels on the plan in Studio, and size the dental air compressor separately with the compressor & vacuum sizing calculator (free tool, coming soon).

Contractor checklist

Before bid

  • Risk category agreed with designer and AHJ
  • Gases listed: N2O, O2, dental air, vacuum, scavenging
  • Separate medical gas permit identified, if your jurisdiction requires one

Before rough-in

  • ASSE 6010 certificates for every installer on site
  • Brazer qualifications submitted
  • ASTM B819 Type L or K tube on site; cleaned and capped
  • Compressor location separate from gas storage, intake clear of vacuum exhaust

During install

  • Labels every 20 ft and at walls
  • Zone valves and alarms located per the drawings
  • Initial pressure, cross-connection and purge tests documented

Before close-in and use

  • 24-hour standing pressure and vacuum tests
  • Alarm tests
  • Third-party verification report to the owner and AHJ
  • Results added to the inspection checklist

Local amendments vary. Las Vegas notes its checklist is basic information and points to the adopted codes (Las Vegas Fire).

How FloorStack helps

The free Studio plan marks gas outlets, zone valves, alarm panels and the compressor location on the floor plan everyone works from. The permit & inspection tracker (free tool, coming soon) will keep the med gas permit, tests and verifier report in one timeline. The compressor & vacuum sizing calculator (free tool, coming soon) will size the dental air and vacuum sources. FloorStack is a vendor-neutral dental build-out platform. See the Dental Office Construction hub and dental office plumbing requirements.

Free tools for this step

Frequently asked questions

Is a dental office with nitrous Category 3?

In King County's examples, a dental office with piped nitrous and/or oxygen is Category 3 (King County).

When does a dental office become Category 2?

King County lists a dental office with oral surgery suites and full sedation, with piped patient gases, as Category 2 (King County).

Who can install dental medical gas piping?

Installers certified to ASSE 6010, with qualified brazers (UpCodes).

Can the installer test their own system?

No. Testing must be done by someone other than the installing contractor before use (Las Vegas Fire).

What pipe is required for nitrous and oxygen?

Hard-drawn seamless copper ASTM B819 medical gas tube, Type L or K (Las Vegas Fire).

How long is the standing pressure test?

24 hours at 20% above operating pressure, with no more than 0.5% leakage (Las Vegas Fire).